Motorisation & IBMS Integration Cheat Sheet

Torque sizing, protocol comparison, wiring & commissioning quick-ref and decision trees on four pages — the working numbers for the desk and the site.

Page 1 · Motor sizing

Torque & motor selection


F = m × g
Load force (N). m = fabric area × mass/m² + bottom bar (+ side-channel friction). g = 9.81.
T(tube) = F × r
r = effective lifting radius = radius to the OUTER fabric wrap, not the bare tube. Largest when rolled up.
T(motor) = T(tube) / η × margin
η = gearbox/assembly efficiency 0.6–0.85. Margin 1.2–1.5× (more for exterior / high-cycle).
Exterior: add windload
Wind force on fabric area (SANS 10160-3) often dwarfs gravity — the governing load for motor, brackets, fixings.

Worked: Sandton boardroom roller

StepValue
Area 2.4 × 3.07.2 m²
Mass (0.35 + 1.8 kg bar)4.32 kg
F = 4.32 × 9.8142.4 N
r (45 mm tube + wrap)0.030 m
T(tube)1.27 Nm
/ 0.70 × 1.32.4 Nm req.
Select6 Nm Sonesse 50
Duty cycle: shading motors are intermittent-rated (~4 min run, then thermal cut-out + cool-down). A motor near its torque limit trips sooner under sun-tracking.
Common Somfy interior Nm ladderTypical use
6 / 10 / 15 NmInterior roller / screen blinds (Sonesse class, quiet)
20 / 30 NmLarger / heavier interior, light exterior (Altus/Orea)
40 / 50 Nm +Heavy / exterior screens, projection, awnings
Page 2 · Protocol & bus comparison

Control bus & integration protocols


Control busTypeFeedbackBest for
Somfy RTS433 MHz 1-way radioNoneResidential / simple retrofit
io-homecontrol~868 MHz 2-way AESYesIntegrated retrofit, feedback
Zigbee2.4 GHz meshYes3rd-party / IoT ecosystems
Dry contactVolt-free relayNoneSafety / global overrides
RS485 / DC wiredWired data busFullLarge new-build integration
Integration protocolModelBlind represented asDoc to require
KNXDecentralised, group addressesDPT objects: move, stop, position %, status, slat %DPT list / ETS project
BACnetObject/property (IP & MS/TP)Analog Value (position), Binary (cmd), Multistate (mode)PICS
ModbusRegister-based master/slaveHolding regs (cmd/position), input regs (status)Register map
Rule: don't pick a protocol in the abstract — match the gateway to what the building's BMS already speaks (BACnet/IP is common in large SA commercial work). Multi-protocol buildings are normal.
Page 3 · Wiring & commissioning quick-ref

Topology & commissioning


Power & cabling

Coincident start: integrated systems move many blinds at once (sun/wind/scene). Check coincident starting current, not just running — stagger group moves or split circuits.
LV DC: SELV + quiet + data-on-cable, but volt-drop over distance is real — size cable & locate PSUs per zone.
Buses: RS485 / KNX TP = daisy-chain + end termination, screened twisted pair, segregate from power.
SA frame: SANS 10142-1 + Certificate of Compliance by a registered person. Define the blind-installer vs electrician trade split.

Commissioning sequence

1. Set limits, verify direction, check travel/noise (every motor)
2. Assign addresses; configure zones/groups
3. Bind gateway objects (ETS / BACnet / Modbus); verify read + write
4. Calibrate sensors; witnessed wind-retraction test (local logic)
5. Tune sun-tracking & daylight; avoid hunting (hysteresis)
6. Program scenes; verify priority hierarchy
7. Integrated test with BMS + lighting; as-builts + training
Page 4 · Decision trees & standards

Choosing the architecture


Control-bus decision tree

BMS position feedback / closed-loop sun-tracking needed?
No, simple/retrofit → RTS (or io if 2-way wanted)
Yes → need feedback
Cabling practical? (new-build, large, RF-hostile) → RS485 / DC wired
Existing building / minimal cabling → io-homecontrol (or Zigbee for IoT)

Intelligence-location rule

Where does the logic live?
Wind / life-safety → LOCAL controller (never BMS-only)
Comfort / energy / scenes → may live in BMS over gateway

Priority hierarchy (top = wins)

1. High-wind / life-safety retraction — LOCAL, pre-empts all
2. Manual override (with timeout to auto)
3. Scheduled scenes
4. Automatic sun / daylight logic

SA / IEC standards quick map

StandardUse
IEC 60335-2-97Drive safety (rolling shutters, awnings, blinds)
IEC 60335-1General appliance safety (used with -2-97)
SANS 10142-1Wiring of premises + CoC
SANS 10160-3Wind actions → exterior load & retract setpoint